Electrical Distribution

 

Series ME07

  • General
  • Technical Table
  • Documentation

AEG ME07 breakers are no more available as the manufacturing is definitely finished. Please see the section RETROFILL ME07 for replacement. Accessories can be still available upon request and check availability on factory.

Description
Two ranges of circuit breakers Series ME for time delayed selectivity with different breaking capacities in each frame size offer a compact and economic solution for all installations.

Standard range S1
The solution for heavy power distribution requirements with sufficiently high breaking capacity for complete time selective discrimination.
High performance range H The compact solution for distribution of extremely high power levels up to 100 kA in industrial and marine installations in each frame size.

Complete line
• Compact, robust steel frame construction which reduces the space requirements within enclosures.
• Circuit breakers and disconnecting switches.
• Fixed and withdrawable versions.
• Appearance of the operator control panel in a modern industry design is identical for the complete productline.
• Drive mechanisms, trip units and accessories e.g. undervoltage trip, shunt trip and auxiliary contacts are common for all frame sizes.
• Manual or motor operated stored energy drive mechanism for direct and remote actuation.
• Microprocessor controlled trip units for advanced protection.
• Bus connection.
Design and specifications are subject to change without notice.

Certifications
ABS, BV, DNV, GL, LRoS, RINA, RMRoS

Conformity
The circuit breakers Series ME07 comply with the standard “Low- voltage switchgear and controlgear” VDE 0660 Part 101, respectively IEC 947-2 and VDE 0113.
The disconnecting switches Series MET are in accordance with the standard “Low-voltage switchgear and controlgear” VDE 0660 Part 107, respectively IEC 947-3 and VDE 0113.

Rated insulation voltage Ui
AC 1000V
Rated impulse withstand voltage Uimp
8kV
Pollution degree
3
Rated voltage Ue
Up to 3 AC 1000V up to DC 750V
Number of poles
3,4
Rated short time current Icw (1.0s
50kA (up till 1250A), 55kA(up till 2500A), 65(up till 3200A)
Switching frequency ops. /h
60
Mechanical endurance (with maintenance x10^3 ops.)
20