Electrical Distribution

 

MCCB type MC9 160-250A

  • General
  • Technical Table
  • Documentation

The MC169 and MC259 breakers have respectively 160A and 250A rated current, in the same size. They can be equipped with thermomagnetic or electronic protection relay, type Line protection, Generator, Magnetic motor protection, isolator.
The electronic protection is a new generation of trip unit, with a very wide range of threshold (from 0,3 to 1 In), and many functions like LS (Long time delay, Short time delay), LSI (with additional Istantaneus protection channel), LSIG (with Ground protection channel).
On the front of the trip unit, there is a micro USB port where it is possible to connect a PC and supply the unit to check the tripping functions.
All the electronic type breakers have the possibility to adjust the Neutral protection as 0%, 50%, 100% of the rated current.

Thermal setting (In) (A)
25-250
Rated insulation voltage Ui (Volts)
750
Rated operational voltage Ue AC/DC
690/500
Ultimate breaking capacity Icu @400/415V AC(kA)
S=50, H=80, X=150,
Category of use
A
Non automatic breaker (Switch)
160A, 250A
Weights
1,6kg 3P; 2,1Kg 4P
Dimensions (w x h x d) mm
3P=105 x 170 x 95 4P=140 x 170 x 95;
Endurance CO operations Mechanical/Electrical at In
160A= 40000/10000; 250A=25000/20000;
Mounting
Fixed, Plug in
Approval / Marking
EN60947-2

Download