Electrical Distribution

 

Loadbreak disconnetors HLN8S, HLN9S, HLN9 up to 4000A

  • General
  • Technical Table

HLN7S - 1600A
HLN8S - 2000A/2500A
HLN9S - 3150A
HLN9 - 4000A

Performance
Panel mounting
Main disconnector
Disconnect function
Visible contact indication
Quick make and quick break mechanism
Independent opening and closing Positive contact indication (PCI)
Defeat mechanism rotary handle
Double knife contacts - high short-circuit resistance
Number of poles 3P - 4P


Standards
IEC 60947-1 and IEC 60947-3, DIN VDE 0660 Teil 107, DIN VDE 0113 Teil 1, BS EN 60947-3, CEI 17-11 (Fasc. 1039), EN 60947-3, NBN EN 60947-3, NF C 63-130

Rated thermal current
1600A-2000A-2500A-3150A-4000A
Rated operational voltage Ue
1000V
Rated insulation voltage Ui
1500V
Peak short withstand circuit current
105kA
Rated short-circuit current
105kA
High 1s rated short time withstand Icw
50kA
Terminal capacity (Cu)
HLN7S,HLN8A:Cu-rail 2x80x10; HLN9S,HLN9:Cu-rail 2x100x10
Approvals / Marking
CE,CESI certificate(HLN7S,HLN8S;HLN9S)